Lennox ALLIED Commercial TCA180S2B Standard Manual page 3

Table of Contents

Advertisement

SPECIFICATIONS
General
Data
Cooling
Gross Cooling Capacity − Btuh
Performance
Net Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
3
Integrated Part Load Value (Btuh/Watt)
Refrigerant
Furnished
Compressor Type (no.)
Electric Heat Available − See page 18 for capacities
Outdoor
Net face area − sq. ft. (m
Coils
Tube diameter − in. (mm)
Outdoor
Coil Fans
Diameter − in. (mm) − No. of blades
Total Air volume − cfm (L/s)
Indoor
Net face area − sq. ft. (m
Coils
Tube diameter − in. (mm)
Drain connection − number & size
Expansion device type
4, 5
Indoor
Nominal motor HP
Blower and
Drive
Selection
Max. usable motor
output (US Only)
Drive Kit
Field Installed Low Static Drive Kit
Blower wheel nominal diameter x width
Filters
No. and size − in. (mm)
Electrical characteristics
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb
entering evaporator air; minimum external duct static pressure.
2
Tested at conditions included in with ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering evaporator air; minimum external
duct static pressure.
3
Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
4
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors fur-
nished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limita-
tions outlined on the motor nameplate.
5
Stocked models are available with standard static drives. High static drives are factory installed (configure to order). Low static drive can be factory installed (configure to order) or
standard static drives can be converted to low static with field installed kit.
Nominal Tonnage
Model No.
Efficiency Type
(kW)
Total Unit Power − kW
1
EER (Btuh/Watt)
Refrigerant Type
Circuit 1
11 lbs. 8 oz. (5.22 kg)
Charge
Circuit 2
11 lbs. 8 oz. (5.22 kg)
Circuit 3
11 lbs. 8 oz. (5.22 kg)
Circuit 4
2
) total
Number of rows
Fins per inch (m)
Motor horsepower (W)
Motor rpm
Total Motor watts
2
) total
No. of rows
Fins per inch (m)
(1) 1 in. NPT coupling
Low Static
Standard Static
High Static
Low Static
Standard Static
High Static
Low Static
Standard Static
#7 − 850−1045 rpm
High Static
#6 − 1045−1285 rpm
Type of filter
20 Ton
TCA240S2B
Standard
243,000 (71.2)
234,000 (68.5)
8000 (3775)
24.1
9.7
10.1
R−22
11 lbs. 8 oz. (5.22 kg)
11 lbs. 8 oz. (5.22 kg)
11 lbs. 8 oz. (5.22 kg)
− − −
11 lbs. 8 oz. (5.22 kg)
Scroll (3)
15, 30, 45, 60 or 90 kW
56.0 (5.2)
3/8 (9.5)
2
20 (787)
(4) 1/3 (249)
1075
1395
(4) 24 (610) − 3
15,450 (7290)
22.3 (2.07)
3/8 (9.5)
3
14 (551)
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
5 hp (3.7 kW)
7.5 hp (5.6 kW)
10 hp (7.5 kW)
5.75 hp (4.3 kW)
5.75 hp (4.3 kW)
8.63 hp (6.4 kW)
8.63 hp (6.4 kW)
11.5 hp (8.6 kW)
11.5 hp (8.6 kW)
#2 − 685− 865 rpm
#2 − 685−865 rpm
#7 − 850−1045 rpm
#6 − 1045−1285 rpm
#9 − 685−865 rpm
#9 − 685−865 rpm
(2) 15 x 15 in. (381 x 381 mm)
Disposable, pleated MERV 7
(6) 24 x 24 x 2 (610 x 610 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
Page 3
TCA240H2B
High
251,000 (73.5)
302,000 (88.4)
240,000 (70.3)
286,000 (83.7)
7500 (3540)
22.2
10.8
11.2
R−22
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
Scroll (4)
56.0 (5.2)
3/8 (9.5)
2
20 (787)
(4) 1/3 (249)
1075
1395
(4) 24 (610) − 3
(4) 24 (610) − 3
15,450 (7290)
16,000 (7550)
22.3 (2.07)
3/8 (9.5)
4
14 (551)
(1) 1 in. NPT coupling
5 hp (3.7 kW)
7.5 hp (5.6 kW)
7.5 hp (5.6 kW)
10 hp (7.5 kW)
10 hp (7.5 kW)
8.63 hp (6.4 kW)
11.5 hp (8.6 kW)
#7 − 850−1045 rpm
#6 − 1045−1285 rpm
#7 − 850−1045 rpm
20 − 25 TON
25 Ton
TCA300S2B
Standard
9000 (4245)
30.1
9.5
9.7
R−22
Scroll (4)
56.0 (5.2)
3/8 (9.5)
2
20 (787)
(4) 1/2 (373)
1075
1800
22.3 (2.07)
3/8 (9.5)
4
14 (551)
N/A
N/A
N/A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents