CS-G90KE
Operation Details
B. PROTECTION
1. PROTECTION CONTROL FOR ALL OPERATIONS
a.
Time Delay Safety Control
•
The compressor is not restarted for 3 minutes after stop of compressor.
b.
30 Second Forced Operation
•
Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control
or Automatic switch.
c.
Total Running Current Control
•
When the outdoor unit total running current (AC) exceeds I1, the frequency is lowered by 1 rank. If I1 is not
exceeded for 30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running
current exceeds I2, the compressor is immediately stopped for 3 minutes.
<Cooling, Soft Dry set value>
Model No.
I1(A)
I2(A)
Note: Zone A will be used 30 minutes after operation starts.
<Heating set value>
Model No.
I1(A)
I2(A)
Zone A
CU-G90KE
CU-G120KE
5.4
7.2
7.3
10.8
38.5°C
CU-G90KE
CU-G120KE
6.2
9.2
7.3
10.8
Zone B
CU-G90KE
CU-G120KE
5.1
6.2
7.3
10.8
Zone B
Outdoor air
temperature
37.5°C
Zone A
– 43 –