Operation Details
5. FAN OPERATION
This operation is to enable the fan operation without compressor running. Timer operation is valid for fan operation.
6. AUTOMATIC OPERATION
When the Automatic mode is selected, the operation mode is decided in accordance to remote control setting
temperature, intake air temperature and outdoor air temperature.
During judging the operation mode, indoor fan is running at Lo– speed and outdoor fan at ON in order to sense
the indoor intake air temperature and outdoor air temperature for 20 seconds. At this time, Power LED is blinking.
After the operation mode is selected, Power LED lights up.
Refer to the examples below, where the remote control setting temperature is 20°C, 25°C and 30°C.
(a) When the remote control setting temperature is 20°C.
Intake Air
Temp.
36
Soft Dry
28
27
t1
t2
20
Heating
16
(°C)
13
19
21
Setting
t1
t2
t3
Temp (°C)
18 and below
+10
+8
-5
19 ~ 22
+8
+7
-7
23 ~ 26
+7
+6
-7
27 and above
+6
+5
-8
Cool
-ing
t3
23
25
Outdoor Air Temp
– 28 –
CS-G90KE