CS-G90KE
Operation Details
(c) Cooling Operation at SHi Speed
During Cooling operation, Indoor Fan speed is set at SHi when the following conditions occur:
•
Outside air temperature is 30°C or above
•
Compressor operates at 72Hz (CU-G90KE) or 78Hz (CU-G120KE) and above
•
Remote control setting fan speed is High
•
Indoor intake air temperature is 24°C or above
•
Remote control setting temperature is 16°C
•
Within 30 minutes after start of operation.
(d) Heating Operation at SSHi Speed
During Heating operation, Indoor Fan speed is set at SSHi when the following conditions occur:
•
Heating operation for 2 hours or more
•
When remote control setting fan speed is High
•
Indoor intake air temperature is 17°C or above and less than 23°C
•
Outdoor air temperature is 4°C or below
•
Remote control setting temperature is 30°C
•
Compressor operates at 92Hz (CU-G90KE) or 98Hz (CU-G120KE) and above
•
Airflow Direction is set at Manual.
8. OUTDOOR FAN CONTROL
•
Outdoor fan motor is controlled with 1 speed only. Fan is in operation when the compressor starts operation and
stops 30 seconds after compressor stops operation.
ON
Compressor
ON
Outdoor Fan
OFF
OFF
30
sec
– 37 –
ON
ON