Operation Details
2. COOLING OPERATION
A. Room Temperature Control
(i) When the remote control setting temperature is less than 24°C.
Cooling
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Outdoor Air Temperature
Model No.
(ii) When the remote control setting temperature is 24°C and above.
Cooling
Intake air temp. –
Internal setting
temp. (°C)
Internal setting temp.
Compressor OFF temp.
Outdoor Air Temperature
Model No.
• Compressor OFF temperature = Compressor ON temperature.
• The operation frequency can be changed every 30 seconds.
• 30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
• The compressor stops when the intake air temperature reaches 1°C below internal setting temperature and continues for
3 minutes.
• When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
• When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
• When the compressor stops, the outdoor fan motor stops 30 seconds later.
83 (Fc max) or 72
+1.5
57
+1.0
48
+0.5
33
0
25
–0.5
25
–1.0
Comp OFF
Less than 38°C
CS-G90KE
83 (Fc max) or 72
+1.5
57
+1.0
48
+0.5
33
0
25
–0.5
25
–1.0
Comp OFF
Less than 38°C
CS-G90KE
– 18 –
Compressor Operation Frequency (Hz)
83 (Fc max) or 72
94 (Fc max) or 78
68
48
36
33
25
Comp OFF
Comp OFF
38°C and above
Less than 38°C
Compressor Operation Frequency (Hz)
83 (Fc max) or 72
94 (Fc max) or 78
57
48
33
25
25
Comp OFF
Comp OFF
38°C and above
Less than 38°C
CS-G90KE
94 (Fc max) or 78
64
70
48
48
33
38
25
33
25
25
Comp OFF
38°C and above
CS-G120KE
94 (Fc max) or 78
64
64
48
48
33
33
25
25
25
25
Comp OFF
38°C and above