Settings; List Of Parameters - Baxi PRIME Series Installation Manual

Condensing gas wall-hung boilers
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
9.

SETTINGS

9.1

List of parameters

In order to view/edit the list of parameters, connect the wireless interface to
the boiler via the X9 connector. Use the SERVICE TOOL software to interface
the portable computer (SERVICE) with the boiler.
Name
Description
AP009
Burner service hours before maintenance warning
Enable/Disable maintenance notifications
- "No service notifications"
AP010
- "Custom service notifications"
- "ABC service notifications"
AP011
Hours the boiler has been electrically switched on
AP016
Enable/Disable central heating
AP017
Enable/Disable domestic hot water
AP025
Enable/Disable demo mode (read-only parameter)
AP026
Delivery temperature setpoint for manual heat request
Summer-winter CH on/off
AP073
(external probe)
AP074
Disable CH (when external probe is connected)
AP079
Level of insulation of the building (external probe)
External temperature below which the anti-freeze protection is
AP080
activated
AP081
Device name acronym
AP082
Winter energy saving activation (read-only parameter)
AP089
Installer's name
AP090
Installer's telephone number
AP107
Colour of display MK2 (read-only parameter)
CP000
Max settable CH setpoint
CP010
CH setpoint
CP020
Zone functionality
CP060
Desired ambient temperature for the zone during the holiday period
Maximum circuit ambient temperature limit in reduced mode that
CP070
allows switching to comfort mode
CP080
Zone temperature set by user
CP081
Zone temperature set by user
CP082
Zone temperature set by user
CP083
Zone temperature set by user
CP084
Zone temperature set by user
CP085
Zone temperature set by user
CP200
Manually set the desired ambient temperature by zone
CP210
Offset of climate curve in comfort mode
CP220
Offset of climate curve in reduced mode
CP230
Climate curve slope
CP240
Zone ambient temperature effect regulation
CP320
Zone operating mode
CP340
Type of reduced night mode
CP510
Temporary ambient temperature value set for the zone
CP550
Fireplace mode active
CP570
Time program selected by the user
CP660
Zone selection icon
CP680
Zone room unit bus channel selection
CP730
Zone heating start boost
CP740
Zone heating off boost
CP750
Maximum pre-heating time [min]
CP780
Zone control strategy selection
DP003
Maximum fan speed in DHW mode
DP005
Storage boiler delivery set value offset
DP006
Storage boiler heating hysteresis ON/OFF
DP007
Three-way valve in standby
7696306 (01-12/17)
X9
Factory
setting
6000
"No service
notifications"
35000
off
off
Normal
40°C
22
off
0
-10
GH 4
Off
-
-
Blue
80
80
Direct circuit
6°C
16°C
16°C
20°C
6°C
21°C
22°C
20°C
20°C
15
15
1.5
3
Manual
Programming
Continuous
Stop request
20°C
off
Prog.1
None
Programming
0
0
0
0
Automatic
selection
7300 (24kW)
8300 (28kW)
20°C
4°C
DHW
36
SERVICE
BO-0000032
Minimum
Maximum
0
51000
-
-
0
51000
off
on
off
on
-
-
80°C
15
30.5
off
on
0
10
-60
60
-
-
-
-
-
-
-
-
-
-
25
80
25
80
-
-
5°C
20°C
5°C
30°C
5°C
30°C
5°C
30°C
5°C
30°C
5°C
30°C
5°C
30°C
5°C
30°C
5°C
30°C
15
90
15
90
0
4
0
10
Temporary
-
request
5°C
30°C
on
Prog.2
Cooling
All
-
1
0
255
0
255
0
180
-
-
1800
9500
0°C
25°C
2°C
15°C
CH
DHW
Level
service
service
service
user
user
user
service
user
user
service
service
service
user
user/
service
user/
service
user
user
user
service
user
service
user
user
user
user
user
user
user
service
service
service
service
user
service
user
user
user
user
user
service
service
service
service
service
service
service
service