Icvc Alert Codes - Carrier 19XRV Start-Up And Service Instructions

With pic iii controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is
necessary.
ICVC FAULT
PRIMARY
STATE
MESSAGE
100
PRESTART
ALERT
101
PRESTART
ALERT
102
PRESTART
ALERT
103
PRESTART
ALERT
104
PRESTART
ALERT
105
PRESTART
ALERT
106
PRESTART
ALERT
107
PRESTART
ALERT
108
PRESTART
ALERT
109
PRESTART
ALERT
110
PRESTART
ALERT
111
PRESTART
ALERT
*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is
the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 4 — ICVC Alert Codes
SECONDARY
PRIMARY CAUSE
MESSAGE
STARTS LIMIT
100Excessive compressor starts
EXCEEDED
(8 in 12 hours).
HIGH BEARING
101Comp Thrust Brg Temp [VALUE]
TEMPERATURE
exceeded limit of [LIMIT]*.
HIGH MOTOR
102Comp Motor Winding Temp
TEMPERATURE
[VALUE] exceeded limit of [LIMIT]*.
HIGH
103Comp Discharge Temp [VALUE]
DISCHARGE
exceeded limit of [LIMIT]*.
TEMP
LOW
104Evaporator Refrig Temp [VALUE]
REFRIGERANT
exceeded limit of [LIMIT]*.
TEMP
LOW OIL
105Oil Sump Temp [VALUE]
TEMPERATURE
exceeded limit of [LIMIT]*.
HIGH
106Condenser Pressure [VALUE]
CONDENSER
exceeded limit of [LIMIT]*.
PRESSURE
LOW LINE
107Percent Line Voltage [VALUE]
VOLTAGE
exceeded limit of [LIMIT]*.
HIGH LINE
108Percent Line Voltage [VALUE]
VOLTAGE
exceeded limit of [LIMIT]*.
GUIDE VANE
109Actual Guide Vane Pos
CALIBRATION
Calibration Required Before Startup.
HIGH
110Rectifier Temperature [VALUE]
RECTIFIER
exceeded limit of [LIMIT]*.
TEMP
HIGH
111Inverter Temperature [VALUE]
INVERTER
exceeded limit of [LIMIT]*.
TEMP
Depress the RESET softkey if additional start
is required. Reassess start-up requirements.
Check oil heater for proper operation.
Check for low oil level, partially closed oil sup-
ply valves, clogged oil filters.
Check the sensor wiring and accuracy.
Check Comp Thrust Brg Alert setting in
SETUP1 screen.
Check motor sensors for wiring and accuracy.
Check motor cooling line for proper operation,
or restrictions.
Check for excessive starts within a short time
span.
Check Comp Motor Temperature Override
setting in SETUP1 screen.
Allow discharge sensor to cool.
Check sensor wiring and accuracy.
Check for excessive starts.
Check Comp Discharge Alert setting in
SETUP1 screen.
Check transducer wiring and accuracy.
Check for low chilled fluid supply
temperatures.
Check refrigerant charge.
Check Refrig Override Delta T in SETUP1
screen.
Check oil heater contactor/relay and power.
Check oil level and oil pump operation.
Check transducer wiring and accuracy.
Check for high condenser water
temperatures.
Check high condenser pressure switch wiring.
Check voltage supply.
Check voltage transformers and switch gear.
Consult power utility if voltage is low.
Check voltage supply.
Check power transformers.
Consult power utility if voltage is high.
Press STOP button on ICVC and perform
Guide Vane Calibration in Controls Test
screen.
Check guide vane actuator feedback
potentiometer.
Check that VFD refrigerant isolation valves
are open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.
Check that VFD refrigerant isolation valves
are open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.
11