Carrier 19XRV Start-Up And Service Instructions page 14

With pic iii controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

CHILLER ALERTS (cont)
ICVC FAULT
PRIMARY
STATE
MESSAGE
159
SENSOR ALERT
161
LOSS OF
COMMUNICATION
162
SENSOR ALERT
163
SENSOR ALERT
164
VFD SPEED ALERT LOW VFD SPEED
165
AUTORESTART
PENDING
166
AUTORESTART
PENDING
167
SYSTEM ALERT
168
SENSOR ALERT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 4 — ICVC Alert Codes (cont)
SECONDARY
MESSAGE
SPARE TEMPERATURE
159Spare Temperature 2
#2
[VALUE] exceeded limit of
[LIMIT]*.
WITH WSM
161WSM Cool Source —
Loss of Communication.
EVAPORATOR
162Evaporator Approach
APPROACH
[VALUE] Exceeded Limit of
[LIMIT]*.
CONDENSER APPROACH 163Condenser Approach
[VALUE] Exceeded Limit of
[LIMIT]*.
164Actual VFD Speed
exceeded limit of Target VFD
Speed –10%.
LOW DC BUS VOLTAGE
165Low DC Bus Voltage:
[VALUE] Exceeded Limit of
[LIMIT]*.
HIGH DC BUS VOLTAGE
166High DC Bus Voltage:
[VALUE] Exceeded Limit of
[LIMIT]*.
HIGH DISCHARGE TEMP 167Comp Discharge Temp
[VALUE] exceeded limit of
[LIMIT]*.
HUMIDITY SENSOR
168Sensor Fault: Check
INPUT
Humidity Sensor Input Sensor.
PRIMARY CAUSE
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check Spare Temp #2 Limit in SETUP1 screen.
Check settings in WSMDEFME screen.
Check CCN communications link with WSM
(Water System Manager) Module.
Check Supervisory Part of WSM.
Check that refrigerant charge level is adequate,
waterbox division plate gaskets are sealing,
evaporator tubes are not fouled and that oil
reclaim system is working.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check Evap Approach Alert setting in SETUP1
screen.
Check sensors resistance or voltage drop.
Check for proper wiring.
Check Cond Approach Alert setting in SETUP1
screen.
Check for noncondensable gas in the
condenser.
Check that the condenser tubes are not fouled.
Actual VFD Speed on COMPRESS screen must
be at least 90% of Target VFD Speed.
Verify phase to phase and phase to ground line
voltage.
Verify phase to phase and phase to ground line
voltage. Monitor AC line for high transient volt-
age conditions.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for excessive starts.
Check Comp Discharge Alert setting in SETUP1
screen.
Check humidity sensor wiring on CCM connec-
tors J3 and J5. CCM switch SW2-1 must be in
"OFF" position.
Check Humidity Sensor Input in Controls Test.
14
ADDITIONAL CAUSE/REMEDY

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents