APPENDIX B
Table D — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS
Wire Type
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.
MS/TP
Network (RS-485)
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
Rnet
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
LEGEND
AWG
— American Wire Gage
CL2P
— Class 2 Plenum Cable
CMP
— Communications Plenum Rated
FEP
— Fluorinated Ethylene Polymer
TC
— Tinned Copper
LOCAL ACCESS TO THE UPC OPEN CONTROL-
LER — The user can use a BACview
play unit or the Virtual BACview software as a local user inter-
face to an Open controller. These items let the user access the
controller network information. These are accessory items and
do not come with the UPC Open controller.
The BACview
6
unit connects to the local access port on the
UPC Open controller. See Fig. F. The BACview software must
be running on a laptop computer that is connected to the local
access port on the UPC Open controller. The laptop will re-
quire an additional USB link cable for connection.
See the BACview Installation and User Guide for instruc-
tions on connecting and using the BACview
To order a BACview
6
Handheld (BV6H), consult Commer-
cial Products i-Vu
Open Control System Master Prices.
®
CONFIGURING THE UPC OPEN CONTROLLER'S
PROPERTIES — The UPC Open device and ComfortLink™
controls must be set to the same CCN Address (Element) num-
ber and CCN Bus number. The factory default settings for
CCN Element and CCN Bus number are 1 and 0 respectively.
— OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Description
6
handheld keypad dis-
6
device.
6
Fig. F — BACview
35
RECOMMENDED VENDORS AND PART NUMBERS
Connect Air
International
W221P-22227
W241P-2000F
W184C-2099BLB
If modifications to the default Element and Bus number are
required, both the ComfortLink and UPC Open configurations
must be changed.
The following configurations are used to set the CCN Ad-
dress and Bus number in the ComfortLink control. These con-
figurations can be changed using the scrolling marquee display
or accessory Navigator handheld device.
Configuration→CCN→CCN.A (CCN Address)
Configuration→CCN→CCN.B (CCN Bus Number)
The following configurations are used to set the CCN Ad-
dress and Bus Number in the UPC Open controller. These con-
figurations can be changed using the accessory BACview
play.
Navigation: BACview→CCN
Home: Element Comm Stat
Element: 1
Bus: 0
TROUBLESHOOTING — If there are problems wiring or
addressing the UPC Open controller, contact Carrier Technical
Support.
Device Connection
Contractors
Belden
RMCORP
Wire and Cable
25160PV
CLP0520LC
82841
25120-OR
6302UE
21450
CLP0442
6
dis-