Annex A (configuration instructions)
16.4 Blockage
16.4.1 Blocking protection
The blocking protection prevents the valve from seizing up. If the actuator stem is in the lower
end position (0 %), it is extended slightly and then moved back to the closed position 24
hours after it last moved.
Movement of the actuator stem caused by the activated blocking protection is indicated by
the yellow LED:
− Protecting against blockage
Settings\Actuator\Blockage
Function
Blocking protection
16.5 Travel
16.5.1 Limited travel range
The 'Limited travel range' parameter determines in % how far the actuator stem can move at
the maximum. The travel determined during initialization acts as the reference.
Settings\Actuator\Travel
Function
Limited travel range
16-4
On
Off
WE
No
WE
100.0 %
Time in s
Adjustment range
Yes/No
Adjustment range
30.0 to 100.0 %
EB 5824-2 EN