Adjusting The Limit Contacts - Samson 5824 Mounting And Operating Instructions

Version with positioner. without fail-safe action, with fail-safe action
Table of Contents

Advertisement

7.3 Adjusting the limit contacts

DANGER
!
Risk of fatal injury due to electric shock
from exposed live parts.
Î Do not touch live parts on adjusting the
limit contacts.
The limit contacts (see the 'Design and prin-
ciple of operation' section) can optionally be
used as make or break contacts.
Terminal assignment (see the 'Installation'
section):
− Terminals 41, 44, 42:
à Bottom cam disk, adjuster 7.1
− Terminals 51, 54, 52:
à Top cam disk, adjuster 7.2
1. Unscrew front cover.
2. Move the actuator stem to the position at
which switching point is to be activated.
3. Use a 4 mm Allen key to turn the adjust-
ers (see the 'Design and principle of op-
eration' section) up to the point where
the contact is triggered.
Tip
The angle of rotation of the cam disks is lim-
ited. Therefore, use preferably the top adjust-
er (7.1) for the upper travel range and the
bottom adjuster (7.2) for the lower travel
range (see Fig. 7-2).
EB 5824-2 EN
Start-up and configuration
7.1
7.2
7.1
Adjuster for limit contact
(bottom contact cam)
7.2
Adjuster for limit contact
(top contact cam)
Fig. 7-2: Adjusters for limit contacts
7-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents