Blockage; Blockage Detection; Blockage Removal - Samson 5857 Mounting And Operating Instructions

Table of Contents

Advertisement

Annex A (configuration instructions)

16.4 Blockage

16.4.1 Blockage detection

Note
The positioner can only detect a valve blockage after either an initialization ('Start-up and
configuration' section) or a transit time measurement ('Service' folder in 'Start-up' or 'Func-
tions') has been performed after the actuator is started up for the first time.
The positioner detects a valve blockage when the actuator stem extends and with absolute
travel adjustment by comparing the travel after the limit switch has been triggered with the
travel measured on initialization. If the comparison shows that the limit switch was triggered
too early, this indicates that there is a valve blockage. The red LED blinks:
− Blockage
Settings\Actuator\Blockage
Function
Blockage detection

16.4.2 Blockage removal

When the Blockage removal function is active, the actuator stem extends and retracts 1 mm
at the adjusted stroking speed three times in sequence. The action is indicated by the yellow
LED (only when the Blockage removal function is active).
− Removing blockage
16-4
On
Off
2
WE
Adjustment range
No
No, Yes
On
Off
4
6
Time in s
Time in s
EB 5857 EN

Advertisement

Table of Contents
loading