Mounting The Actuator; Type 5824: Force-Locking Attachment; Type 5824: Form-Fit Attachment - Samson 5824 Mounting And Operating Instructions

Version with positioner. without fail-safe action, with fail-safe action
Table of Contents

Advertisement

Installation
ment needs to be changed when a three-
way mixing valve is used.
Driving pin in position 0,
location of scale with globe or three-way
diverting valves (delivered state)
Fig. 5-2: Travel indication scale
Globe and three-way diverting valves:
the driving pin is in position 0 (delivered
state).
Three-way mixing valve:
change the alignment of the scale.
Î Carefully open the front cover.
Tip
We recommend screwing the bottom screws
of the open housing front cover into the top
holes of the housing.
Î Remove scale, turn it and replace it so
that the pin is positioned over the appro-
priate hole (6, 12 or 15) corresponding
to the rated travel (6, 1 or 15 mm travel).
Î Close front cover.
5-2
Hole for driving pin
with three-way mixing
valve

5.4 Mounting the actuator

The actuator is mounted either directly onto
the valve or using a yoke depending on the
valve version used (see Fig. 5-3).
5.4.1
Type 5824: force-
locking attachment
1. Turn the handwheel (2) counterclockwise
to retract the actuator stem.
2. Place the actuator on the valve connec-
tion and fasten with the coupling nut (4).
Tightening torque
NOTICE
!
Risk of actuator damage due to unautho-
rized opening of the back housing cover.
Î Do not open the back housing cover.
5.4.2
Type 5824: form-fit
attachment
1. Place the actuator on the yoke and fasten
with the coupling nut (4).
Tightening torque
Place actuator with yoke (15) on the
valve and fasten with the nut (17).
Tightening torque
2. Pull plug stem until it reaches the actua-
tor stem or extend actuator stem using
the handwheel (2).
20 Nm
20 Nm
150 Nm
EB 5824-2 EN