Table 1: N2 Bus Objects
Point Name
a
Room Temp
Aux Temp/Outdoor Temp
a, g
Heating SP
(Occupied Heating SP)
a, g
Cooling SP
(Occupied Cooling SP)
a, g
Setback Heating SP
(Unoccupied Heating SP)
a, g
Setback Cooling SP
(Unoccupied Cooling SP)
Minimum Heat SP
a
Maximum Heat SP
a
Minimum Cool SP
Maximum Cool SP
a
Fan
a
Mode
a
Occupancy
W1 State
W2 State
Y1 State
Y2 State
G State – Fan
a, c
Temp Units
(Local Display Only)
Continued on the next page . . .
4
TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions
TEC Point
Type/
Address
ADI-1
a
ADI-2
ADI-3
ADI-4
ADI-5
ADI-6
ADI-7
ADI-8
ADI-9
ADI-10
BD-1
BD-2
BD-3
BD-4
BD-5
BD-6
BD-7
BD-8
BD-9
N30/NAE
BAS Model
Object
Point Type
Type
N2 AI
CSAD
N2 AI
CSAD
N2 AO
CSAD
N2 AO
CSAD
N2 AO
CSAD
N2 AO
CSAD
N2 AI
CSAD
N2 AO
CSAD
N2 AO
CSAD
N2 AI
CSAD
N2 BO
CSBD
d, e
N2 MSO
CSMS
N2 BO
CSBD
N2 BI
CSBD
N2 BI
CSBD
N2 BI
CSBD
N2 BI
CSBD
N2 BI
CSBD
N2 BO
See
Footnote c.
Override Range
32 to 122°F (0 to 50°C)
-40 to 122°F (-40 to 50°C)
40 to 90°F (4.5 to 32°C)
54 to 100°F (12 to 37.5°C)
40 to 90°F (4.5 to 32°C)
54 to 100°F (12 to 37.5°C)
40°F (4.5°C)
40 to 90°F (4.5 to 32°C)
54 to 100°F (12 to 37.5°C)
100°F (37.5°C)
0 = Auto, 1 = On
0 = Off, 1 = Cool, 2 = Heat, 3 = Auto
0 = Unoccupied, 1 = Occupied
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = °C, 1 = °F