Table 2: Installer Configuration Menu (Cont.)
Sets the Minimum Heating/Cooling
Deadband
Deadband
Default: 2.0°F (1.1°C)
set? Y/N
See the Setting the Heating/Cooling
Deadband (Deadband) section.
Determines How the Fan Activates in
Response to a Call for Heat
Fan cont
Default: Thermostat Controls Fan (On)
set? Y/N
See the Setting the Fan Control
(Fan cont) section.
Delays Fan Termination at Cycle's End
for 60 Seconds
Fan del
Default: No Delay (Off)
set? Y/N
See the Setting the Fan Delay
(Fan del) section.
Sets the N2 Address
N2 addr
Default: 253
set? Y/N
See the Setting the N2 Address
(N2 addr) section.
Sets the Duration for Temporary
Occupancy Time
ToccTime
Default: Three Hours (3.0 hrs)
set? Y/N
See the Establishing the Temporary
Occupancy Time (ToccTime) section.
Room Air Sensor Calibration (Offset)
Cal RS
Default: 0.0°F (0.0°C)
set? Y/N
See the Room Air Sensor Calibration
(Cal RS) section.
Auxiliary/Outdoor Air Sensor
Calibration (Offset)
Cal OS
Default: 0.0°F (0.0°C)
set? Y/N
See the Auxiliary
Temperature/Outdoor Air Sensor
Calibration (Cal OS) section.
Disable/Enable Second Heating Stage
H Stage
Default: Two Stages
set? Y/N
See the Disable/Enable Second
Heating Stage (H Stage) section.
8
TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions
Disable/Enable Second Cooling Stage
C Stage
Default: Two Stages
set? Y/N
See the Disable/Enable Second
Cooling Stage (C Stage) section.
Disables Heating Operation based on
Auxiliary/Outdoor Air Temperature
H lock
Default: 120°F (49°C)
set? Y/N
See the Setting the Heating Lockout
(H lock) section.
Disables Cooling Operation based on
Outdoor Air Temperature
C lock
Default: -40°F (-40°C)
set? Y/N
See the Setting the Cooling Lockout
(C lock) section.
Sets the Economizer Changeover
Temperature
Chngstpt
Default: 55°F (13°C)
set? Y/N
See the Setting the Economizer
Changeover Temperature (Chngstpt)
section.
Sets the Outdoor Air Damper Minimum
Position
Min pos
Default: 0%
set? Y/N
See the Setting the Outdoor Air
Damper Minimum Position (Min pos)
section.
Sets the Mechanical Cooling Mode
C mech
Default: Off
set? Y/N
See the Setting the Mechanical
Cooling Mode (C mech) section.
Sets the Mixed Air Temperature
Setpoint
Mix stpt
Default: 55°F (13°C)
set? Y/N
See the Setting the Mixed Air
Temperature Setpoint (Mix stpt)
section.
Displays the Mixed Air Temperature
Display
Default: N/A
MS? Y/N
See the Displaying the Mixed Air
Temperature (Display) section.