Commissioning/service reports
Hydraulic parameter report
Setting and test values
Frost protection (brine medium)
Testing external secondary circuit pumps
Circulation pump type
Circulation pump stage
Overflow valve setting
Commissioning, primary circuit
Flow temperature, primary circuit
("Diagnosis" Ó "System overview")
Return temperature, primary circuit
("Diagnosis" Ó "System overview")
Calculated flow rate
Temperature differential (primary circuit flow/
return) ΔT:
■ With secondary circuit flow temperature =
35 °C and primary circuit flow temperature
= 10 °C
■ With secondary circuit flow temperature =
35 °C and primary circuit flow temperature
= 0 °C
Testing the mixer, heat pump and cylinder heating
Checked under the following conditions:
Room temperature
Outside temperature
Temperature "Cylinder temp. top" constant?
Secondary circuit flow temperature
Temperature differential ΔT
"Secondary flow temp." / "Sec. return
temp."
108
Set value
°C
–15
°C
°C
kg/h
Minimum
flow rate to
specification
K
3 to 5
K
2 to 4
°C
°C
Yes (±1 K)
°C
Rising
K
6 to 8
Commis-
sioning
from
to