Hydraulic parameters report
Setting and test values
Frost protection (brine medi-
um)
Testing the external heating circuit pumps
Circulation pump type
Circulation pump stage
Overflow valve setting
Commissioning, primary circuit
Primary circuit flow tempera-
ture
("Diagnosis" Ó "System over-
view")
Primary circuit return tempera-
ture
("Diagnosis" Ó "System over-
view")
Temperature differential (pri-
mary circuit flow/return) ΔT:
■ If secondary circuit flow tem-
perature = 35 °C primary cir-
cuit flow temperature = 10 °C
■ If secondary circuit flow tem-
perature = 35 °C primary cir-
cuit flow temperature = 0 °C
Testing the mixer, heat pump and cylinder heating
Checked under the following conditions:
Room temperature
Outside temperature
Temperature "Cylinder temp.
top" constant?
Secondary circuit flow tempera-
ture
Temperature differential ΔT
"Flow temp. secondary" / "Re-
turn temp. sec."
Commissioning/service reports
Setpoint
°C
–19
°C
°C
K
3 to 5
K
2 to 4
°C
°C
Yes (±1 K)
°C
Rising
K
6 to 8
Commis-
Mainte-
sioning
nance/Serv-
ice
From Open From Open