Commissioning/Service Reports - Viessmann Vitocal 300-G Pro SPS Installation And Service Instructions For Contractors

Table of Contents

Advertisement

Commissioning reports
Settings in the delivered condition
Parameter
Parameter location
group
Heat pump
Config./ Configuration Plant Fault, low pressure
Config./ Configuration Plant Fault, high pressure
Config./ Configuration Plant Fault, frost threshold,
Fixed value
Config./ Heat pump param-
eters
Config./ Heat pump param-
eters
Config./ Heat pump param-
eters
Heat pump system expan-
sion valve (requires expert
password)
Heat pump system expan-
sion valve (requires expert
password)
Config./ Heat pump param-
eters
Config./ Heat pump param-
eters
System/Groundwater (heat
source)
System/Groundwater (heat
source)
System/Heat pump/Logger/
Definition (requires pass-
word)
Time settings
Time settings
Description
Value
-15 °C
threshold
65 °C
threshold
-10 °C
evaporator for geo-
thermal probe
Fault, frost threshold,
3 °C
evaporator if heat is
not drawn from geo-
thermal probe
Maximum flow tem-
75 °C
perature, control unit
Start delay
180 s
Restart delay
900 s
Overheating set val-
6 °K
ue
EEV position at start-
1 %
up
Evaporator pump ad-
45 s
vance runtime (pri-
mary circuit)
Fault, primary circuit
5 s
flow, response delay
Groundwater pump
20 s
advance runtime
Fault, flow, response
5 s
delay
Data recording inter-
60 s
val
Start delay
3 min
Restart blocking time 15 min

Commissioning/service reports

Commission-
ing
Mainte-
nance/
Service
85