Installation sequence

Routing cables to the heat pump wiring chamber

Danger
Damaged cable insulation can
cause injury and damage to the
appliance.
Route cables so that they cannot
touch very hot, vibrating or sharp-
edged components.
Danger
Incorrect wiring can lead to seri-
ous injury from electrical current
and result in appliance damage.
■ Route LV leads < 42 V and
> 42 V/230 V~/400 V~ cables
separately.
■ Strip the insulation from the
cables just ahead of the termi-
nals, and bundle tightly to the
corresponding terminals.
■ Secure cables with cable ties/
strain relief fittings.
This ensures that, should there
be a fault, for example when
detaching a wire, the wires can-
not drift into the adjacent voltage
area.
38
When routing the on-site power cables,
observe the location of the cable entries
into the appliance through its back panel
(see page 19).