Controller And Sensor Pcb (Sensors) - Viessmann Vitocal 300-A Installation And Service Instructions Manual

Air/water heat pump with electric drive, 400 v~
Table of Contents

Advertisement

Installation sequence
Electrical connections, heat pump controller

Controller and sensor PCB (sensors)

Set the required parameters during commissioning:
see page 55 onwards.
Plug
Sensor/component
F0.1/F0.2
Outside temperature sensor
F0.2/F0.3
Radio clock receiver (accessories)
F4
Buffer temperature sensor
F6
Cylinder temperature sensor, top
(X25.5/X25.6)
F7
Cylinder temperature sensor, bottom
(X25.7/X25.8)
F8
Secondary circuit flow temperature sensor
(X25.9/X25.10)
F11
Contact humidistat 24 V
Note
If a 230 V~ contact humidistat (connection to X3.8/X3.9) is used for cooling,
insert a jumper, otherwise the heat pump will not start (message "CA Pro-
tectn device primry").
F12
Flow temperature sensor, heating circuit with mixer M2/HC2
F13
Flow temperature sensor, system (downstream of the heating water buffer
cylinder and external heat generator)
F14
Flow temperature sensor, cooling circuit (heating circuit without mixer A1/HC1
or separate cooling circuit SKK)
F16
Room temperature sensor, cooling circuit
Required for separate cooling circuit SKK
Recommended for heating/cooling circuit without mixer A1/HC1
F20
Boiler water temperature sensor, external heat generator
F26
Buffer temperature sensor, cooling
aVG
KM-BUS (wires interchangeable)
Use the KM-BUS distributor (accessories) if several devices are connected.
KM-BUS subscriber (examples):
Mixer extension kit for heating circuit M3/HC3
Vitotrol 200-A or Vitotrol 300 remote control unit: Set heating circuit assign-
ment at the remote control.
EA1 extension, AM1 extension
Communication interface Vitocom 100, type GSM2
Modbus 2 (wires not interchangeable)
sVA
Connection for photovoltaic system electricity meter
PWM signal, secondary pump
a:DB
PWM signal, cylinder loading pump
a:DC
J3
Jumper for terminator Modbus 2
Terminator enabled (delivered condition)
Terminator disabled
J4
Jumper for setting master/slave Modbus 2
Heat pump controller is slave.
Heat pump controller is master (delivered condition).
38
(cont.)
Type
NTC 10 k
Ω
DCF
NTC 10 k
Ω
NTC 10 k
Ω
NTC 10 k
Ω
Pt500A
(PTC)
NTC 10 k
Ω
NTC 10 k
Ω
NTC 10 k
Ω
NTC 10 k
Ω
NTC 10 k
Ω
NTC 10 k
Ω