Installation sequence
Electrical connection
Terminals
Function
211.2
Secondary pump
211.4
3-way diverter valve for "Central heat-
ing/DHW heating"
r
M
In conjunction with the cylinder load-
ing system:
Cylinder loading pump
■
2-way shut-off valve
■
M
Internal unit: Controller and sensor PCB (sensors)
Set the required parameters during commissioning:
See from page 47.
Sensors
Plug
Sensor
F0.1/F0.2
Outside temperature sensor
F0.2/F0.3
Radio clock receiver (accessories)
F4
Buffer temperature sensor
F6
Cylinder temperature sensor, top
(X25.5/X25.6)
F7
Cylinder temperature sensor, bottom
(X25.7/X25.8)
F11
Contact humidistat 24 V
Note
If a 230 V~ contact humidistat (connection to X3.8/X3.9) is used
for cooling, insert a jumper, otherwise the heat pump will not
start (message "CA Protectn device primry").
F13
Flow temperature sensor, system (downstream of the heating wa-
ter buffer cylinder and external heat generator)
F14
Flow temperature sensor, cooling circuit (heating circuit without
mixer A1/HC1 or separate cooling circuit SKK)
F16
Room temperature sensor, cooling circuit
■
■
F20
Boiler water temperature sensor, external heat source
28
(cont.)
–
Required for separate cooling circuit SKK
Recommended for heating/cooling circuit without mixer A1/HC1
Explanation
Connection values
Max. output: 130 W
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
■
In systems without a heating water buffer cylinder, no
■
other heating circuit pump is required (see terminal
212.2).
Connect the temperature limiter to restrict the maxi-
■
mum temperature for underfloor heating systems in
series (see page 23).
Secondary pump is connected at the factory. Connect
the temperature limiter on site.
Connection values
Max. output: 130 W
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
■
3-way diverter valve is connected at the factory. Con-
nect cylinder loading pump in parallel on site.
Type
NTC 10 k
Ω
DCF
NTC 10 k
Ω
NTC 10 k
Ω
NTC 10 k
Ω
―
NTC 10 k
Ω
NTC 10 k
Ω
NTC 10 k
Ω
NTC 10 k
Ω