2.1.2 Analog Output Unit
■
Features of the Analog Output Unit
The analog output unit converts its internal data into analog values to be output to inverters or
other analog-driven equipment.
● The number of channels is four.
● The output range can be selected from the following seven types.
Voltage output: -10 to +10 V, 0 to +10 V, -5 to +5 V, 0 to +5 V, +1 to +5 V
Current output: 0 to +20 mA, +4 to +20 mA
● The digital conversion processing speed is 50 μs.
● The resolution is 1/25,600 to 1/ 64,000.
Digital values set for conversion are converted into a maximum of 16-bit analog data.
■
Optional Functions
This product is provided with the following option setting functions.
Function
Offset / Gain processing
function
Scale conversion function
Clipping function
Analog output hold
function in STOP mode
WUME-GM1AIO-01
Specifications
Performs the correction of offset values (addition correction) or gain values
(magnification correction).
This function is to scale-convert values to an easy-to-use analog output range.
Sets in advance the upper limit and lower limit for the analog output value.
Holds the analog output when the operation mode of the GM1 Controller changes
from RUN to STOP.