4.3 Setting the Analog Input Unit

4.3.1 List of Analog_8IN Parameters

The following table shows a list of changeable parameters for the GM1 Analog Input Unit.
Set parameter for each channel.
Setting item
ConversionProcess
RangeSetting
AveragingProcess
AverageConstant
OffsetGainProcess
OffsetValue
Gain value
ScaleConversion
ScaleConversionMaxValue
ScaleConversionMinValue
UpperAndLowerLimitCompariso
n
WUME-GM1AIO-01
Default
Description
Execute
Select "Execute / Not Execute" of the analog input.
Select the input range.
-10 to +10 V
0 to +10 V
-5 to +5 V
-10 to +10 V
0 to +5 V
+1 to +5 V
0 to +20 mA
+4 to +20 mA
Select the operation for input average processing.
Not execute
No averaging / Count-based average / Time-based
average / Moving average
Specify the constant for input average processing
Count-based average
200
Time-based average
Moving average
Select "Execute / Not Execute" for the Offset / Gain
Not Execute
processing.
Specify the offset value for when the Offset / Gain
processing is executed.
0
-3000 to +3000
Specify the gain value for when the Offset / Gain
10000
processing is executed.
(multiplied by 1.0)
+9000 to +11000 (multiplied by 0.9 to 1.1)
Select "Execute / Not execute" for the scale
Not execute
conversion.
Specify the maximum value after scale conversion is
executed.
10000
-32768 to +32767
Specify the minimum value after scale conversion is
executed.
0
-32768 to +32767
Select "Execute / Not Execute" for the upper limit /
Not Execute
lower limit comparison.

4.3 Setting the Analog Input Unit

Average count: 2 to 60,000 [times]
Average time: 1 to 1,500 [ms]
Average count: 2 to 2,000 [times]
4-7