To test the HVAC system
The installer uses this setting to test the HVAC system.
Press SELECT to open INSTALLER TEST.
1
NOTE The HOME and SELECT buttons are replaced with MODE and CANCEL buttons.
.
Press MODE to cycle through OFF, COOL, HEAT, and EHEAT.
2
NOTES
The availability of the modes are based on the installer configuration settings.
○
The selected MODE operates each equipment stage for 3 minutes.
○
The center of the display counts down the number of seconds remaining for the current stage of
○
equipment operation.
When the countdown reaches zero, if another stage exists, the banner text changes to 2ND STAGE and a
○
new 180-second countdown timer starts. If no other stage exists, the test cycle ends and the MODE is
set to OFF.
When HEAT or EHEAT modes are running and there is a configured humidifier, the output that controls
○
the humidifier is energized.
When COOL mode is running and a dehumidifier has been configured for operating a HumidiMiZer™, the
○
output configured for the dehumidifier output is energized.
Press CANCEL to turn off the currently running equipment and transition the screen to the installer menu
3
selections.
After 20 minutes of inactivity (no button presses by the installer), INSTALLER TEST terminates, and the home
screen displays.
NOTES
•
EHEAT is only a choice when a heat pump is selected in the configuration.
•
HEAT is not available in a cooling-only configuration.
•
COOL is not available in a heating-only configuration.