Appendix A: BACnet Points List
Point Name
IR Proximity Sensitivity
Sound Effect
Number of Parts in Schedule
Day
Occupied Fan Mode
Unoccupied Fan Mode
Current Fan Mode
Indoor Equipment Type
Outdoor Equipment Type
Remote Sensor Type
Dehumidification Type
Occupancy Output Terminal
Humidification Output
Terminal
Dehumidification Output
Terminal
Smart Recovery
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX
Installation Guide
Point Access
Units
4=AUTO
5=E-HEAT
READ_WRITE
1=HIGH
2=MEDIUM
3=LOW
READ_WRITE
1=OFF
2=CLICK
3=BEEP
READ_WRITE
1=2 PARTS
2=4 PARTS
READ_WRITE
1=AUTO
2=ON
READ_WRITE
1=AUTO
2=ON
READ_WRITE
1=AUTO
2=ON
3=OVERRIDE AUTO
4=OVERRIDE ON
READ_ONLY
1=NO INDOOR
2=FURNACE
3=AIR HANDLER
GATED_WRITE
1=NO OUTDOOR
2=A/C
3=HEAT PUMP
GATED_WRITE
1=NONE
2=OUTDOOR
3=SPACE
4=AVERAGE
5=OCCUPANCY
6=FAULT_INPUT
7=SAT
GATED_WRITE
1=NO
2=YES
3=OVRCRL(2F)
4=HUMIDIMIZER
GATED_WRITE
1=OFF
2=Y3
3=O/B
4=W2
GATED_WRITE
1=OFF
2=Y3
3=O/B
4=W2
GATED_WRITE
1=OFF
2=Y3
3=O/B
4=W2
GATED_WRITE
1=NO
2=30 MIN
3=60 MIN
4=90 MIN
BACnet Point Name
PROX_SENS
SOUND
SCHED_DAY_PARTS
OCC_FAN
UNOCC_FAN
FAN MODE
ID_EQUIP_TYPE
OD_EQUIP_TYPE
REMOTE_SENSOR
DEHUM_TYPE
OCC_OUTPUT
HUM_OUTPUT
DEHUM_OUTPUT
SMART_RECVRY
56
BACnet
Object ID
MSV:401
MSV:402
MSV:403
MSV:404
MSV:405
MSV:406
MSV:500
MSV:501
MSV:502
MSV:503
MSV:504
MSV:505
MSV:506
MSV:507
CARRIER CORPORATION ©2021
All rights reserved

Advertisement