Installation, Start-Up, and
IMPORTANT: Read entire instructions before starting
the installation.
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Fol-
low all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Im-
proper wiring or installation may damage thermostat.
Recognize safety information. This is the safety alert sym-
bol
. When the safety alert symbol is present on equip-
ment or in the instruction manual, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety alert sym-
bol. DANGER identifies the most serious hazards which will
result in severe personal injury or death. WARNING signi-
fies a hazard which could result in personal injury or death.
CAUTION is used to identify unsafe practices which would
result in minor personal injury or property damage.
GENERAL
The commercial, programmable thermostats are wall-
mounted, low-voltage thermostats which maintain room tem-
perature by controlling the operation of an HVAC (heating,
cooling and ventilation) system. Separate heating and cool-
ing set points and auto-changeover capability allow occu-
pied and unoccupied programming for energy savings.
All thermostats allow up to 4 time/temperature settings to
be programmed per 24-hour period. Each thermostat stores
programs for 3 different days (Saturday, Sunday, and Mon-
day through Friday). Batteries are not required. During power
interruption the internal NEVERLOST™ memory stores pro-
grammed schedules for an unlimited time while the clock
continues to run for at least 48 hours.
The thermostat can be configured to accept several
different equipment configurations, including heat pump
operation.
NOTE: The thermostat is not factory-configured for use in
heat pump applications. The advanced setup must be per-
formed to configure the thermostat for use with heat pump
units.
INSTALLATION
Select Thermostat Location —
be mounted:
• approximately 5 ft from the floor
• close to or in a frequently used room, preferably on an
inside partitioning wall
• on a section of wall without pipes or ductwork
• where temperature operating limits are within 41 to 104 F
(5 to 40 C)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
4
PC 111
Tab
11a 13a
Commercial Programmable Thermostat
Operating Instructions
Part Number 33CSSP2-WC
The thermostat should
Catalog No. 533-346
Printed in U.S.A.
• where humidity operating range is within 0 to 95% rela-
tive humidity, non-condensing
The thermostat should NOT be mounted:
• close to a window, on an outside wall, or next to a door
leading to the outside
• where exposed to direct light and heat from a lamp, the
sun, a fireplace, or any other temperature-radiating object
which may cause a false reading
• close to or in direct airflow from supply registers or return-
air grilles
• in areas with poor air circulation (such as behind a door or
in an alcove)
Install Thermostat
Before installing thermostat, turn off all power to the
unit. There may be more than one power disconnect.
Electrical shock can cause injury or death.
1. Turn off all power to unit.
2. If an existing thermostat is being replaced:
a. Remove existing thermostat from the wall.
b. Disconnect wires from existing thermostat. Do not
allow wires to fall back into the wall. As each
wire is disconnected, record wire color and terminal
connection.
c. Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and must be
disposed of properly.
3. Remove the thermostat cover from wall plate (mount-
ing base) to expose mounting holes. See Fig. 1.
3 1/8"
MOUNTING
HOLE
B
O
R
G
Y1 W2
W1
Y2
3 1/8"
HOLE FOR
WIRING
Fig. 1 — Thermostat Mounting and Wiring
Form 33CS-31SI
Pg 1
Debonair™
33CS
1"
WIRING
TERMINAL
BLOCK
C
MOUNTING
HOLE
2-99
Replaces: New

Advertisement

Table of Contents
loading

Summary of Contents for Carrier Debonair 33CS

  • Page 1 Debonair™ 33CS Commercial Programmable Thermostat Installation, Start-Up, and Operating Instructions Part Number 33CSSP2-WC • where humidity operating range is within 0 to 95% rela- IMPORTANT: Read entire instructions before starting tive humidity, non-condensing the installation. The thermostat should NOT be mounted: •...
  • Page 2: Heat Pump Configuration

    4. Route thermostat wires through large hole in mounting THERMOSTAT TYPICAL UNIT base. Remove outer sheath from wires for added flex- ibility. Standard solid or multi-conductor thermostat wire should be used from the thermostat to the unit. Size and length considerations are as follows: for a maximum distance from unit of 36 ft, use 22 AWG (American Wire Gage) wire;...
  • Page 3 Table 1 — Thermostat Wiring Terminations THERMOSTAT TYPICAL UNIT EXISTING WIRE TERMINAL FUNCTION DESIGNATION CONNECTION G or F Y1, Y, or C Cooling 24 VAC COMMON W1, W, or H Heating W1/O/B FAN RELAY Rh, R, M, Vr, or A Power (24 v) COMPRESSOR RELAY Common...
  • Page 4: Install Accessories

    ELECTRIC HEAT CONFIGURATION (Step 7) — Step 7 2. The cooling set point for Occupied 1 will be displayed. is used to configure the thermostat for electric heat. The vari- Use the UP ARROW and DOWN ARROW buttons to able can be configured ON or OFF. The default is OFF. raise or lower the cooling set point until the desired tem- perature is shown.
  • Page 5: Calibrate Sensor

    9. The On/Off icon will be displayed. Use the UP Calibrate Sensor — Every thermostat is factory cali- ARROW to turn the Occupied 1 period ON for this day. brated. Under normal circumstances there will never be a Use the DOWN ARROW to turn the Occupied 1 period need to re-calibrate the thermostat.
  • Page 6: Auto Changeover

    If Fan On is not selected, the fan will only operate during OPERATION heating or cooling operation. The Mode button selects the operating mode of the ther- mostat. If OFF is selected, the thermostat will not enter Heat- Emergency Heat —...
  • Page 7: Troubleshooting

    TROUBLESHOOTING Table 4 — Troubleshooting PROBLEM SOLUTION Display on thermostat not illuminated. Check for 24 vac at the R terminal connection. Terminal R must be connected for proper thermostat operation. Cooling will not energize. Select COOL mode. Decrease cooling set point to 10 degrees below room temperature.