Setting
NET GP Y3 MODE—Select Network General Purpose Output Y3 for control over the
BACnet network.
Setting the mode to:
OFF (disabled) sets the Present Value of the BACnet object to inactive and read-only
and the corresponding output relay will be in a de-energized state.
ACTV (energized active) allows BACnet writes to the Present Value and energizes the
output relay when the Present Value is active
INAC (energized inactive) allows BACnet writes to the Present Value and energizes
the output relay when the Present Value is inactive. If a Network General Purpose
Output timeout occurs, the Present Value goes to the inactive state and the relay is
either energized ACTV or de-energized INAC depending on the mode.
The outputs have primary assignments:
Y3 - 3rd stage cooling
W2 - 2nd stage heating
OB - Heat pump reversing valve
If any of these outputs are required by the system configuration for their primary
function, they are available for optional equipment (humidifier, dehumidifier, and
occupancy output). Any output that is still available after configuring primary and optional
equipment can be made available as a BACnet network-controlled output.
This setting is not displayed if BACnet is disabled.
NET GP W2 MODE—Select the Network General Purpose Output W2 mode for control
over the BACnet network. Setting the mode to OFF (disabled) sets the Present Value of
the BACnet object to Inactive and read-only and the corresponding output relay will be in
a de-energized state.
Setting the mode to:
OFF (disabled) sets the Present Value of the BACnet object to inactive and read-only
and the corresponding output relay will be in a de-energized state.
ACTV (energized active) allows BACnet writes to the Present Value and will energize
the output relay when the Present Value is active.
INAC (energized inactive) allows BACnet writes to the Present Value and will energize
the output relay when the Present Value is inactive. If a Network General Purpose
Output timeout occurs, the Present Value goes to the inactive state and the relay is
either energized ACTV or de-energized INAC depending on the mode.
The outputs have primary assignments:
Y3 - 3rd Stage cooling
W2 - 2nd Stage heating
OB - Heat Pump reversing valve
If any of these outputs are required by the system configuration for their primary
function, they are available for optional equipment (humidifier, dehumidifier and
occupancy output). Any output that is still available after configuring primary and optional
equipment can be made available as a BACnet network-controlled output.
This setting is not displayed if BACnet is disabled.
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX
Installation Guide
43
Using installer settings
Default/Range
D:
OFF (disabled)
R:
OFF (disabled)
ACTV (energized active)
INAC (energized inactive)
D:
OFF (disabled)
R:
OFF (disabled)
ACTV (energized active)
INAC (energized inactive)