1-7. INDOOR UNIT CONNECTION CHECK

This function is available J-IIIL, J-III, J-II and J-IIS series.
● It is necessary to stop SERVICE TOOL (UTY-ASGX) and WEB MONITORING TOOL (UTY-AMGX), when
you will carry out indoor unit connection check.
1) After verifying that the system is normally, press the MODE/EXIT button (SW107) once.
LED105
LED104
2) Press the SELECT button (SW108) to display "F3" on the LED104.
(Monitoring mode)
LED105
LED104
*1
(The display of the LED104 changes each time the SELECT button is pressed.)
*1 : The "F1" and "F9" modes are used for maintenance, so do not set them in regular
3) When "F3" appears on the LED104, press the ENTER button (SW109).
LED105
LED104
A flashing display appears on the LED105.
4) Press the SELECT button (SW108) to display "12" on the LED105.
LED105
LED104
5) When "12" appears on the LED105, hold down the ENTER button (SW109) for at least 3
seconds. (Unless it is held down for at least 3 seconds, the selection will not be confirmed.)
When the Indoor Unit Connection Check function is activated, the display changes to "run".
LED105
LED104
● When the Indoor Unit Connection Check function is not activated (during maintenance), the
display changes to "FAIL".
LED105
LED104
6) When Indoor Unit Connection Check is completed, the number of indoor unit is displayed on
the LED104, LED105. Verify that the count matches the number of indoor units being installed.
LED105
LED104
Ex.) When eight indoor units are being connected
Note
LED105
LED104
(Setting mode)
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
- (07-62) -
(Function mode)
LED105
LED104
(Error history mode)
LED105
LED104
*1