Function Setting; Function Details - Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

2-9. FUNCTION DETAILS

Function
Function
number
00
Filter
indicator
11
01
interval
02
00
Filter
01
indicator
13
action
02
00
Ceiling
20
airflow
01
00
Vertical
airflow
23
01
direction
Horizontal
00
swing
01
24
airflow
02
direction
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
Static pressure
26
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
31
00
Cool air tem-
01
30
perature trigger
02
00
01
Heat air tem-
31
perature trigger
02
03
Setting number
Default
Standard
Longer
Shorter
Enable
Disable
Display only on
central remote
control
Standard
High Ceiling
Standard
Raise
Standard
Left half
Right half
SP mode 00
SP mode 01
SP mode 02
SP mode 03
SP mode 04
SP mode 05
SP mode 06
SP mode 07
SP mode 08
SP mode 09
SP mode 10
SP mode 11
SP mode 12
SP mode 13
SP mode 14
SP mode 15
SP mode 16
SP mode 17
SP mode 18
SP mode 19
SP mode 20
SP mode 21
SP mode 22
SP mode 23
SP mode 24
SP mode 25
SP mode 26
SP mode 27
SP mode 28
SP mode 29
Normal SP
Standard
Adjust (1)
Adjust (2)
Standard
Adjust (1)
Adjust (2)
Adjust (3)
- (07-129) -
Adjust the filter cleaning interval notification. If the notification is too
early, change to setting 01. If the notification is too late, change to
setting 02.
Enable or disable the filter indicator.
Setting 02 is for use with a central remote control.
Regulate the airfl ow according to the needs of the installation location.
When set to 01, the air flow will be stronger. (Cassette type only)
Adjust the vertical airflow direction. All airflow direction louvers are
adjusted together.
(Cassette type only)
Adjust the horizontal swing airflow direction.
(For horizontal swing equipped models)
Range of static
Model name
pressure
ARXK04GCLH
SP mode 00 to 03
ARXK07GCLH
ARXK09GCLH
SP mode 00 to 03
ARXK12GCLH
ARXK14GCLH
ARXK18GCLH
SP mode 00 to 05
ARXK24GCLH
ARXD04GALH
ARXD07GALH
ARXD09GALH
SP mode 00 to 09
(0 to 90 Pa)
ARXD12GALH
ARXD14GALH
ARXD18GALH
SP mode 00 to 05
ARXD24GALH
(0 to 50 Pa)
ARXA24GBLH
SP mode 00 to 14
ARXA30GBLH
ARXA36GBLH
SP mode 00 to 12
ARXA45GBLH
SP mode 00 to 11
ARXC36GBTH
SP mode 02 to 16
ARXC72GBTH
SP mode 04 to 27
ARXC90GBTH
SP mode 05 to 24
ARXC96GATH
SP mode 05 to 29
ARXN18GATH
SP mode 05 to 10
ARXN24GATH
SP mode 05 to 15
ARXN30GATH
ARXN34GATH
SP mode 05 to 25
ARXN36GATH
ARXN45GATH
ARXN018GLBH
SP mode 00 to 08
ARXN024GTBH
SP mode 00 to 10
ARXN030GTBH
Please refer to "Chapter04 7.FAN PERFORMANCE CURVE" for the
characteristics of each indoor unit.
Adjust the cool air trigger temperature. To lower the trigger
temperature, use setting 01. To raise the trigger temperature,
use setting 02.
Adjust the heat air trigger temperature. To lower the trigger
temperature by 6 degrees C, use setting 01. To lower the trigger
temperature by 4 degrees C, use setting 02. To raise the trigger
temperature, use setting 03.
Details
Normal static
pressure
10Pa
10 Pa
15 Pa
25Pa
40Pa
50Pa
60Pa
100Pa
150Pa
50Pa
60Pa
50Pa

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents