Installing Insulation; Filling With Putty; Test Run; Indoor Unit Connection Check - Fujitsu Airstage AJ 040LCLDH Series Installation Manual

Outdoor unit
Hide thumbs Also See for Airstage AJ 040LCLDH Series:
Table of Contents

Advertisement

(1) Calculation of additional amount for pipe length
Total length of ø 9.52
mm liquid pipe
a × 0.058
(kg/m)
A =
m
Total
=
(2) Calculation of total refrigerant amount
C = A+B =
NOTES:
Check the total refrigerant amount under the following conditions
Condition
Model
AJ*040LCLDH
Total amount of
AJ*045LCLDH
refrigerant
AJ*054LCLDH
<Calculation>
Outdoor unit: AJ*054LCLDH
(1) Calculation of additional amount for outdoor unit
If liquid pipe piping length is the following
Ø 9.52 mm: 20 m, Ø 6.35 mm: 10 m
Additional charge volume:
A = 20 m × 0.058 kg/m +10 m × 0.021 kg/m = 1.37 kg
(2) Check the total amount of refrigerant
C = A + B = 1.37 kg + 4.0 kg = 5.37 kg ≤ 6.83 kg
→No problem if the above condition is satisfied.

8.4. Installing insulation

• Install insulation material after conducting the "8.1 Sealing test".
• To prevent condensation and water droplets, install insulation material on the refrigerant
pipe.
• Refer to the table to determine the thickness of the insulation material.
• If the outdoor unit is installed at a level that is higher than the indoor unit, the water that
has condensed in the 3-way valve of the outdoor unit could travel to the indoor unit.
Therefore, use putty in the space between the pipe and the insulation to prevent the
entry of water.
Table. Selection of insulation
(Use an insulation material with equal heat transmission rate or below 0.040
W/(m·k))
Insulation material minimum thickness (mm)
Relative humidity
≤ 70%
Pipe diameter
6.35
8
(mm)
9.52
9
12.70
10
15.88
10
* When the ambient temperature and relative humidity exceed 32°C (DB) and 85%
respectively, please strengthen heat insulation of refrigerant pipe.

8.5. Filling with putty

WARNING
Fill the piping holes and wiring holes
with putty (locally purchased) to avoid
any gap (Fig A). If small animals such
as insects enter the external unit, a
short circuit may be caused near elec-
trical components in the service panel.
If the outdoor unit is installed at a level
that is higher than the indoor unit, the
water that has condensed in the 3-way
valve of the outdoor unit could travel
to the indoor unit. Therefore, use putty
in the space between the pipe and the
insulation to prevent the entry of water
to the indoor units.
En-15
Total length of ø 6.35
mm liquid pipe
+
m
kg
(Round up A to 2 decimal place)
kg
(B: Factory charged amount)
kg
Computational formula
C ≤ 6.83 kg
≤ 75%
≤ 80%
10
13
11
14
12
15
12
16
Fig. A
Putty

9. TEST RUN

a × 0.021

9.1. Indoor unit connection check

(kg/m)
Normal operation will not be possible without performing the Indoor unit connection check.
9.1.1 Things to confi rm before starting the Indoor unit connection
kg
check
To ensure safety, check that the following work, inspections and operations have been
completed.
1
Check that all work on the wiring connecting the outdoor
unit and indoor units has been completed.
2
Is a breaker installed at the power supply cable of out-
door unit and every indoor units?
3
Are the cables connected to the terminals without loose-
ness, and in accordance with the specifications?
4
Are all the indoor units stopped? Indoor unit connection
check cannot be performed if any unit is operating.
5
Is the connection to Service tool (UTY-ASGX) and Web
monitoring tool (UTY-AMGX) stopped?
9.1.2 Operating procedure for Indoor unit connection check
Please perform the indoor unit connection check according to following procedures.
The Indoor unit connection check can be completed within several minutes.
Turn on the power of indoor
unit and outdoor unit.
≤ 85%
17
18
19
20
Insulation
Check Item
: Press the "MODE/EXIT" button
: Press the "SELECT" button
: Press the "ENTER" button.
: Press the "ENTER" button for
more than 3 seconds.
Set to Function mode [F3].
(When [F4] to [F9] are displayed, continue to press
the "SELECT" button until [F3] is displayed.)
Press the "SELECT" button until "12" is displayed.
Press the "ENTER" button for more than 3 seconds.
When indoor unit connection
check cannot be performed
This will be displayed when the Indoor unit connection
check starts.
Confirm the number of connected indoor units and the
volume ratio of the indoor units connection.
(*1) The number of connected indoor units
Ex.) When 8 units are connected
(*2) Volume ratio of the indoor units connection
Ex.) When the ratio is 120%
Exit indoor unit connection check mode.
When error occurs
Please refer to the following "Error displays"
for details.
When it finishes normally, nothing will be displayed on
7-segment display.
Check Column