Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual page 861

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
Energy saving
3
0
level setting
Capacity
priority setting
4
0
(in low noise
mode)
Low noise
4
1
mode setting
Low noise
mode
4
2
operation level
setting
Recovery
6
0
operation
*1: Do not set this for outdoor units with Slave setting.
*2: Applicable only for the outdoor unit that has 2 compressors.
Recovery operation is operable when the outdoor unit has 2 compressors within a same system.
LED104
Setting Function
CODE No.
0
0
Level 1 (stop)
Level 2 (operated at
0
1
40% capacity)
Level 3 (operated at
0
2
60% capacity)
Level 4 (operated at
0
3
80% capacity)
Level 5 (operated at
0
4
100% capacity)
0
0
Off (quiet priority)
0
1
On (capacity priority)
0
0
Off (Normal)
0
1
On (Low noise mode)
0
0
Level 1 (55dB)
0
1
Level 2 (50dB)
0
0
On
0
1
Off
- (07-80) -
Outdoor unit
Factory
setting
Master Slave
l
The capacity limit can be
selected by the external
input terminal (CN133) when
operating with the "Energy
-
¡
Saving Peak Cut function."
*1
The lower the level, the more
the effect of energy saving, but
the cooling/heating performance
will also drop.
If the cooling/heating
performance becomes
insufficient when the low noise
l
mode is set, it is possible to
-
set "capacity priority" that
¡
*1
automatically cancels the low
noise mode (once performance
is restored, the mode will
automatically return to the low
noise mode).
l
-
¡
*1
l
The noise level when operating
-
¡
in the low noise mode can be
*1
set.
If one of compressor fails,
l
-
backup operation will be
¡
*1
performed by the remaining
compressors as emergency. *2
NOTE:
In the VRF system with multiple outdoor units,
the recovery operation is unable to activate
if any one of the outdoor units, in which all
compressors are malfunctioned, breakdowns
due to the uncontrollable pressure equalization
between the outdoor units.
If in the event that the recovery operation were to
operate under the malfunctioned condition, it will
lead to accumulation of refrigerant in the faulty
outdoor unit.
Remarks