Selection table
Examples for panel
connection versions
861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
12

Panel connection

12.1

Features

• Bushings for plugs with inside-cone plug-in system according to EN 50181
• Single and multiple connections possible per phase
• Conection of several cables with different plug sizes possible per phase
• Connection of solid-insulated or gas-insulated bar possible
• Connection of 4MT7 voltage transformer plugged in at the panel connection housing
version 3
• Connection of 4MU3 voltage transformer via flexible cable and plug size 2 at the panel
connection housing
• For rated normal currents up to 2500 A
12.2

Cable plugs for panel connection versions

Plug size
Rated normal current
Rated lightning impulse withstand voltage
Rated short-duration power-frequency
withstand voltage
Min. cross-section
Min. core diameter
Max. cross-section
Max. core diameter
Min. diameter across insulation
Max. diameter across insulation
Meaning of the item numbers in the
illustrations for the panel connection versions
Panel connection housing
Subframe
Version 1
Version 2
S2
A
800
kV
200
kV
95
2
25
mm
mm
4.9
2
325
mm
mm
22.3
mm
13.5
mm
40
S2
1
S3
1
Description
S3
S4
1250
2500
200
200
95
95
50
95
7.2
9.3
800
1200
34.6
45.4
15.5
33
51.0
66
25/214