Siemens 8DA10 Series Installation And Operating Instructions Manual page 199

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

Indicatio
VOIS+, VOIS R+
n
L1
L2
L3
A0
A1
A2
A3
A4
-
A5
-
A6
-
A7
-
A8
-
1
LED does not light up,
861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
Fig. 214: CAPDIS-S2+: Cover closed
Fig. 215: CAPDIS-S2+: Cover opened
CAPDIS-S1+
L1
L2
L3
L1
L2
-
LED lights up
CAPDIS-S2+
Description of the indication
L3
State of the
1
relay contacts
Red
Green
U ≠ 0
U = 0
Operating voltage not present.
U ≠ 0
U = 0
Operating voltage present.
U ≠ 0
U = 0
• Operating voltage not present.
• Auxiliary voltage not available (only CAPDIS-S2+).
U ≠ 0
U = 0
Failure in phase L1, operating voltage at L2 and L3
(for CAPDIS-Sx+ also earth-fault indication).
U ≠ 0
U = 0
Voltage (not operating voltage) present.
U ≠ 0
U = 0
Indication: "Test" passed (lights up shortly).
U ≠ 0
U = 0
Indication: "Test" not passed (lights up shortly).
U ≠ 0
U = 0
Overvoltage present (lights up permanently).
U ≠ 0
U = 0
Indication: "ERROR" e.g. in case of missing auxiliary voltage.
Operation
"Test" button
Cover
LC display
LEDs red and green
(state of the relay contacts)
Duct for signaling cables CAPDIS-M
Test socket L2
Earth socket
Test socket L3
Test socket L1
Short instructions
199/214