861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
➭ Protect the junction edges of panels without busbar earthing switch with additional sealing
ledges ① . Tightening torque of the bolts: 12 Nm. Stick a sealing strap ② under the sealing
ledge.
Fig. 160: Example: Fastening the sealing ledge on
the junction edge between two panels
➭ Attach sealing straps and fasten an angle between an intermediate panel and a panel with
make-proof busbar earthing switch. Tightening torque: 12 Nm.
Fig. 161: Example: Fastening an angle between intermediate panels and panels
with make-proof earthing switches (basic scheme)
Angle (2 bolts M6x25)
Busbar earthing switch
Sealing strap
Sealing ledge (4 bolts M6x25)
Sealing strap