Operation
1
Initial situation
3
➭
Switch the left-hand three-position disconnector to CLOSED position
(insert the operating lever for the DISCONNECTING function and turn
180° clockwise).
5
➭
Push the right-hand control gate to the left.
7
➭
Remove the operating lever for the DISCONNECTING function.
The right-hand control gate returns to its initial position.
176/214
37.3
Switching operations in top-mounted bus sectionalizer
(without additional panel)
Coupling busbar sections
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
➭
Push the left-hand control gate to the left.
4
➭
Remove the operating lever for the DISCONNECTING function.
The left-hand control gate returns to its initial position.
6
➭
Switch the right-hand three-position disconnector to CLOSED position
(insert the operating lever for the DISCONNECTING function and turn
180° clockwise).