10. COMMUNICATION FUNCTION

10.2.4 Test operation mode

(1) How to prepare and cancel the test operation mode
(a) Preparing the test operation mode
Set the test operation mode type with the following procedure.
1) Selection of test operation mode
Transmit the command [8] [B] + data No. [0] [0] + data to select the test operation mode.
2) Check of test operation mode
Read the test operation mode set for the slave station, and check that it is set correctly.
a) Transmission
Transmits command [0] [0] + data No. [1] [2].
b) Return
The slave station returns the preset operation mode.
POINT
The test operation mode is used to check operation. Do not use it for actual
operation.
If communication stops for longer than 0.5 s during test operation, the servo
amplifier decelerates to a stop, resulting in servo-lock. To prevent this, continue
communication all the time by monitoring the status display, etc.
Even during operation, you can switch the servo amplifier to the test operation
mode. In this case, switching to the test operation mode will shut off the base
circuit to coast the motor.
Command
Data No.
[8] [B]
[0] [0]
Note. Refer to section 10.2.5 for the output signal (DO) forced output.
Command
Data No.
[0] [0]
[1] [2]
0
0
0
Transmission
data
0004
Output signal (DO) forced output (Note)
0005
Single-step feed
Reading test operation mode
0: Normal mode (not test operation mode)
1: JOG operation
2: Positioning operation
3: Motor-less operation
4: Output signal (DO) forced output
5: Single-step feed
10 - 21