Terminal Connection - Mitsubishi FR-A800-E Instruction Manual

Table of Contents

Advertisement

Terminal connection diagrams
2.4
Terminal connection diagrams
FM type
Sink logic
Main circuit terminal
Control circuit terminal
MCCB
Three-phase
AC power
supply
Control input signals
(No voltage input allowed)∗1
Forward rotation start
Reverse rotation start
Start self-holding selection
High speed
Multi-speed
Middle speed
selection
Low speed
Jog operation
Second function selection
Output stop
Reset
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
power failure
Contact input common
24VDC power supply
(Common for external power supply transistor)
24V external power
supply input
Common terminal
Frequency setting signals (Analog)
3
Frequency setting
2
potentiometer
1/2W1kΩ∗4
1
Auxiliary
(+)
(-)
input
Terminal 4 input
(+)
(Current input)
(-)
Connector for plug-in option connection
Safety stop signal
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common
22
INSTALLATION AND WIRING
Jumper
P1
P/+
Reactor
MC
R/L1
S/L2
T/L3
ON
OFF
Main circuit
Earth
(Ground)
Control circuit
STF
STR
STP(STOP)
RH
RM
RL
∗2
JOG
RT
MRS
RES
AU
CS
SD
PC
+24
SD
Voltage/current
∗3
input switch
10E(+10V)
ON
OFF
10(+5V)
DC0 to 5V
Initial value
2
DC0 to 10V selectable
DC0 to 20mA
5
(Analog common)
DC0 to ±10V
1
DC0 to ±5V selectable
DC4 to 20mA
4
DC0 to 5V
selectable
DC0 to 10V
Connector 1 Connector 2
Connector 3
Shorting
24V
wire
PC
S1
S2
Output shutoff
circuit
SIC
SD
Brake unit
(Option)
N/-
U
Inrush current
V
limit circuit
W
EMC filter
ON/OFF
∗9
connecter
C1
B1
A1
C2
B2
A2
RUN
Running
SU
Up to frequency
IPF
Instantaneous
power failure
OL
Overload
FU
Frequency detection
SE
24V
PU
connector
F/C
USB A
(FM)
∗7
connector
2
4
SD
∗3
USB
mini B
AM
connector
5
Initial value
Ethernet
∗3
connector
∗10
Initial value
∗3
∗10
So (SO)
SOC
Motor
M
Earth (Ground)
Relay output∗5
Relay output 1
(Fault output)
Relay output 2
Open collector output∗6
Open collector output common
Sink/source common
+
-
Indicator
(Frequency meter, etc.)
Calibration
Moving-coil type
resistor ∗8
1mA full-scale
(+)
Analog signal output
(0 to ±10 VDC)
(-)
Safety monitor output
Safety monitor output common

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents