Connection of motor with encoder (vector control)
• Position control
Vector control dedicated motor (SF-V5RU, SF-THY), 12 V complementary
Positioning unit
MELSEC-Q QD75P[ ]N/QD75P[ ]
MELSEC-L LD75P[ ]
FLS
RLS
DOG
STOP
CLEAR
PULSE F
PULSE R
CLRCOM
PULSE COM
RDYCOM
COM
READY
Torque limit command

The pin number differs according to the encoder used.
Speed, control, torque control, and position control by pulse train input are available with or without the Z-phase being connected.

Connect the encoder so that there is no looseness between the motor and motor shaft. Speed ratio must be 1:1.

Earth (ground) the shield of the encoder cable to the enclosure using a tool such as a P-clip. (Refer to

For the complementary, set the terminating resistor selection switch to OFF position. (Refer to

A separate power supply of 5 V/12 V/15 V/24 V is necessary according to the encoder power specification.
When the encoder output is the differential line driver type, only 5 V can be input.
Make the voltage of the external power supply the same as the encoder output voltage, and connect the external power supply across PG and
SD.

For terminal compatibility of the FR-JCBL, FR-V7CBL, and FR-A8AP, refer to

For the fan of the 7.5 kW or lower dedicated motor, the power supply is single phase. (200 V/50 Hz, 200 to 230 V/60 Hz)

Connect the recommended 2W1k resistor between terminal PC and OH. (Recommended product: MOS2C102J 2W1k by KOA Corporation)
Insert the input line and the resistor to a 2-wire blade terminal, and connect the blade terminal to terminal OH. (For the recommended 2-wire
blade terminals, refer to
Insulate the lead wire of the resistor, for example by applying a contraction tube, and shape the wires so that the resistor and its lead wire will not
touch other cables. Caulk the lead wire securely together with the thermal protector input line using a 2-wire blade terminal. (Do not subject the
lead wire's bottom area to an excessive pressure.)
To use a terminal as terminal OH, assign the OH (external thermal O/L relay input) signal to an input terminal. (Set "7" in any of Pr.178 to Pr.189.
For details, refer to the FR-A800 Instruction Manual (Detailed).)

Assign the function using Pr.178 to Pr.184, Pr.187 to Pr.189 (input terminal function selection).
 When position control is selected, terminal JOG function is invalid and simple position pulse train input terminal becomes valid.
 Assign the function using Pr.190 to Pr.194 (output terminal function selection).
58
INSTALLATION AND WIRING
Three-phase
AC power supply
MCCB
MC
Three-phase
AC power
supply
Forward stroke end
Reverse stroke end
Pre-excitation/servo on
Clear signal
Pulse train
Sign signal
24VDC power supply
Preparation ready signal
(+)
(±10V)
(-)
page
40.)
When OH signal is assigned to terminal RH
(Pr.182 = "7")
Insulate
Resistor (2 W1kΩ)
Insulate
MCCB
MC
∗7
R/L1
U
Inverter
S/L2
V
W
T/L3
PC
External thermal protector
2W1kΩ
relay input
∗8
RH(OH)
SD
STF
FR-A8AP
STR
PA1
LX
∗9
PA2
CLR
∗9
PB1
JOG
∗10
PB2
NP
∗9
Differential
PZ1
line driver
PC
PZ2
SE
PG
Complementary
SD
Terminating
resistor
PG
ON
RDY
∗11
SD
5
∗4
∗6
OFF
1
page
57.
RH (OH)
PC
2-wire blade terminal
To thermal protector
OCR
SF-V5RU, SF-THY
A
B
FAN
C
U
V
IM
W
E
Earth
(ground)
Thermal
protector
G1
G2
∗1
A
B
C
D
PLG
F
G
∗2
S
R
∗3
12VDC
(+)
(-)
∗5
power supply
page
59.)
page
55.)