E2: Communication Error Between Ms Box And Master Unit - Midea VRF Series Service Manual

Table of Contents

Advertisement

2.3 E2: Communication error between MS box and master unit

Digital display output
Description
 Communication error between MS box and master outdoor unit.
 All units stop running.
 Error code is only displayed on the master unit.
Trigger / recover condition
 Trigger condition: MS box and outdoor units cannot communication for 2 minutes after the system power on 20 minutes.
 Recover condition: Communication go back to normal.
 Reset method: Resume automatically.
Possible causes
 Communication wires between MS box and outdoor units not connected properly.
 MS box power supply abnormal.
 Loosened wiring within electric control box.
 The sequence of the PQE signal lines is incorrect.
 Interference from high voltage wires or other sources of electromagnetic radiation.
 Communication wire too long.
 Damaged outdoor main PCB or electric control box communication terminals block.
V6R VRF 50/60Hz