4.3 Parameters of Excess and Insufficient Refrigerant System

Under the following conditions, the operating parameters given in Tables 6‐4.4 and 6‐4.5 should be observed: 
 The master outdoor unit can detect all the indoor units. 
 The number of indoor units displayed on DSP2 is steady and is equal to the actual number of indoor units installed. 
 All stop valves are open and all indoor unit EEVs are connected to their unit's PCB. 
 If the combination ratio is 100% or less, all the indoor units are currently running and if the combination ratio is more 
than 100%, indoor units with total capacity equal to the total capacity of the outdoor units are currently running. 
 If  the  outdoor  ambient  temperature  is  high,  the  system  is  being  run  in  cooling  mode  with  the  following  settings: 
temperature 17°C; fan speed high. 
 If  the  outdoor  ambient  temperature  is  low,  the  system  is  being  run  in  heating  mode  with  the  following  settings: 
temperature 30°C; fan speed high. 
 The system has been running normally for more than 30 minutes. 
 There parameters are more reliable in cooing only mode. 
Table 6‐4.4: Outdoor unit operating parameters in excess refrigerant system 
Outdoor ambient temperature (T4 )
Discharge pressure (Pc)
Suction superheat (T7-Te)
Discharge superheat (DSH)
Table 6‐4.5: Outdoor unit operating parameters in insufficient refrigerant system 
Outdoor ambient temperature (T4 )
Discharge pressure (Pc)
Suction superheat (T7-Te)
Discharge superheat (DSH)
 
°C
≥41 
31 to 41
MPa
≥3.5 
≥3.4 
°C
≤3 
≤3 
°C
≤11 
≤ 15 
°C
≥41 
31 to 41
MPa
≤3.0 
≤2.6 
°C
≥18 
≥15 
°C
≥35 
≥35 
V6R VRF 50/60Hz
<10 
26 to 31
10 to 26 
≥2.8 
≥ 2.6 
≥2.4 
≤3 
≤3 
≤3 
≤ 15 
≤ 15 
≤ 17 
<10 
26 to 31
10 to 26 
≤2.4 
≤2.3 
≤2.2 
≥15 
≥12 
≥12 
≥30 
≥30 
≥30 
 
165