Low Noise Mode; 8.6 Power Limitation Mode - Midea VRF Series Service Manual

Table of Contents

Advertisement

V6R VRF 50/60Hz

8.5 Low Noise Mode

Low noise mode is used to decrease the noise produced by outdoor units. There are 3 kinds of low noise mode: night silent
mode, silent mode and super silent mode. When low noise mode activating, both the fan step and compressor are limited.
In order to maintain the reliability of V6R system, the lowest fan step for inverter module temperature protection is prior to
low noise control.
Table 3-8.4: Low noise mode
Night silent mode
ODU
Max. Fan step
8HP
22
10HP
23
12HP
24
14HP
22
16HP
23
18HP
24
20HP
22

8.6 Power Limitation Mode

The energy saving mode is used to limit the system power. It can be used to limit the line selection current or to reduce the
peak current.
Table 3-8.5: Power limitation mode
Power limitation mode setting
n41
n42
n43
n44
n45
n46
n47
50
Max. frequency step
Max. Fan step
Cooling mode 59
Heating mode 68
Cooling mode 67
Heating mode 78
Cooling mode 72
Heating mode 80
Cooling mode 90
Heating mode 106
Cooling mode 90
Heating mode 118
Cooling mode 102
Heating mode 120
Cooling mode 59
Heating mode 68
Power limitation mode level
Level 1 (Default)
Level 2
Level 3
Level 4
Level 5
Level 6
Level 7
Silent mode
Max. frequency step
Cooling mode 59
22
Heating mode 68
Cooling mode 67
23
Heating mode 78
Cooling mode 72
24
Heating mode 80
Cooling mode 90
22
Heating mode 106
Cooling mode 90
23
Heating mode 118
Cooling mode 102
24
Heating mode 120
Cooling mode 59
22
Heating mode 68
Super silent mode
Max. Fan step
Max. frequency step
Cooling mode 52
19
Heating mode 52
Cooling mode 56
20
Heating mode 56
Cooling mode 64
21
Heating mode 72
Cooling mode 77
19
Heating mode 86
Cooling mode 79
20
Heating mode 106
Cooling mode 90
21
Heating mode 109
Cooling mode 52
19
Heating mode 52
Correction factor
100%
90%
80%
70%
60%
50%
40%