2.25 PL, C7: Inverter module temperature protection
Digital display output
Description
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition:
For PL protection: Refer to Part 3 6.5 Inverter Module Temperature Protection Control
For C7 protection: PL protection appears three times in 100 minutes.
Recover condition:
Refer to Part 3 6.5 Inverter Module Temperature Protection Control
Reset method:
For PL protection: Resume automatically.
For C7 protection: Manually restart.
Possible causes
Blocked, dirty or loose heat sink.
Inverter module damaged.
Procedure
The inverter module heat sink is blocked
The screws connecting the heat sink to
the inverter module are loose
Replace the inverter module
PL / C7
or dirty
No
No
Yes
Clean or replace the heat sink
Tighten the screws and make sure the
Yes
heat sink is well-connected
V6R VRF 50/60Hz