Menu Mode Function - Midea VRF Series Service Manual

Table of Contents

Advertisement

V6R VRF 50/60Hz

Menu mode function:

Table 5-2.3: Menu mode function
Digital display
content
n11
Test operation
n14
Cooling test
n15
Heating test
n16
Maintenance mode
n17
Manual defrost
n18
Automatic refrigerant diagnosis
n21
Refrigerant recovery 1 (PUMP DOWN)
n22
Refrigerant recovery 2 (PUMP OUT)
n25
Auto refrigerant charging
n27
Vacuum mode
n31
History error codes
n32
Cleaning history error codes
n33
Fan software version
Factory reset (Except when snow blowing
n34
and reverse rotation for dust cleaning)
n35
Release emergency stop
n41
Power limitation mode 1
n42
Power limitation mode 2
n43
Power limitation mode 3
n44
Power limitation mode 4
n45
Power limitation mode 5
n46
Power limitation mode 6
n47
Power limitation mode 7
Auto regulation of medium capacity
n91
(Tes0=6,default)
n92
Auto regulation of high capacity (Tes0=3)
n93
Auto regulation of low capacity (Tes0=9)
n94
Low locking capacity (Tes0=9)
n95
Medium-to-low locking capacity (Tes0=6)
n96
Medium locking capacity (Tes0=3)
n97
Medium-to-high locking capacity (Tes0=0)
n98
High locking capacity (Tes0=-3)
Auto regulation of medium capacity
nA1
(Tcs0=48,default)
nA2
Auto regulation of high capacity (Tcs0=50)
nA3
Auto regulation of low capacity (Tcs0=45)
64
Menu mode
Only available for the master unit
Only available for the master unit (all indoor units running in cooling mode)
Only available for the master unit (all the indoor units will run in heating mode. Once
there is one or more old indoor unit in the system)
Only available for the master unit, the system does not check the indoor units' number.
Only available for the master unit
Only available for the master unit
Only available for the master unit
Only available for the master unit
Only available for the master unit
Only available for the master unit
Display recent ten history error codes
Only available for the master unit
Only available for the master unit
Only available for the master unit, 100% capacity output
Only available for the master unit, 90% capacity output
Only available for the master unit, 80% capacity output
Only available for the master unit, 70% capacity output
Only available for the master unit, 60% capacity output
Only available for the master unit, 50% capacity output
Only available for the master unit, 40% capacity output
Only available for master unit (Te target temperature during cooling operation, Automatic
control)
Only available for master unit (Te target temperature during cooling operation, Automatic
control)
Only available for master unit (Te target temperature during cooling operation, Automatic
control)
Only available for master unit (Te target temperature during cooling operation, Automatic
control)
Only available for master unit (Te target temperature during cooling operation, Locking)
Only available for master unit (Te target temperature during cooling operation, Locking)
Only available for master unit (Te target temperature during cooling operation, Locking)
Only available for master unit (Te target temperature during cooling operation, Locking)
Only available for master unit (Tc target temperature during heating operation, Automatic
control)
Only available for master unit (Tc target temperature during heating operation, Automatic
control)
Only available for master unit (Tc target temperature during heating operation, Automatic
control)
Remarks
Table continued on next page ...

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents