V6R VRF 50/60Hz
2.30 CB1, CB2, CB3, CB4: Overmatch protection
Digital display output
Description
CB1: VRF indoor exceeds the match range (the highest priority)
CB2: AHU kit exceeds the match range (second highest priority)
CB3: HT exceeds the match range (third highest priority)
CB4: The total connection ratio exceeds the match range (the fourth highest priority)
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition
Trigger condition: the indoor unit connection ration exceeds the match table below.
Recover condition: the indoor unit connection ration in the range of the match table.
Reset method: Manually restart.
Table 6-2.1: Match table
IDU1
IDU2
/
VRF indoor
HT
/
AHU kit
/
Notes:
1.
X is 205 for single outdoor unit system; X is 155 for 2 outdoor units combination system; X is 135 for 3 outdoor units combination units system
Possible causes
Connection ratio does not meet the requirements.
Procedure
144
Total
IDU3
connection
ratio A(%)
1
/
40 ≤ A ≤ X
/
40 ≤ A ≤ 205
AHU kit
40 ≤ A ≤ X
1
/
40 ≤ A ≤ 115
CB1, CB2, CB3, CB4
Change indoor unit connection ratio
IDU1
IDU2
connection
connection
ratio B(%)
ratio C(%)
1
40 ≤ B ≤ X
/
40 ≤ B ≤ X
1
C ≤ 105
40 ≤ B ≤ X
1
/
/
/
IDU3
connection
Note
ratio D(%)
/
Connect at least
/
one VRF Indoor
C ≤ 65
D ≤ 115