Installation
98/214
➭ If not yet pre-assembled, mount the adapter plate on the voltage transformer.
NOTE
The already assembled adapter plate can be displaced due to vibrations during transport.
To position the adapter plate correctly:
➭ Loosen the M8 bolts of the adapter plate a little bit.
➭ Bolt the adapter plate uniformly together with the voltage transformer mounting plate.
Tightening torque: 30 Nm.
➭ Insert the silicone adapter in the voltage transformer.
ATTENTION
Risk of partial discharges at the outside-cone bushing.
➭ Make sure that the connecting lug of the capacitive connecting point of the outside-cone
bushing is earthed.