Room dimensions and
wall distances
Load-bearing capacity
of the floor
864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06
Fig. 36:
Wall-standing arrangement
Fig. 37:
Free-standing arrangement
* Depending on national requirements
** Lateral wall distance ≥ 500 mm optionally required on the left or on the right
*** Lateral minimum wall distance ≥ 100 mm optionally possible on the left
or on the right
Load data and minimum distances
Constant loads
Not constant loads
Minimum distances
Minimum door opening
*) Depending on national requirements.
**) Optionally possible on the left or on the right.
***) Optionally required on the left or on the right.
****) Without busbar components / height of low-voltage compartment 850 mm
*****) Individual panel without transport packing
(for group deliveries and bringing in with transport packing, see page 57, "Transport units "
Vertical single load
Live load
Control aisle
Minimum lateral wall distance
Lateral wall distance
Ceiling height
Height
Width
12 kN ****)
2
9 kN/m
800 mm *)
100 mm **)
500 mm ***)
2900 mm
2700 mm ****)
900 / 1900 mm *****)
Installation
51/214