Installation
Fig. 104: Cleaning and greasing the silicone adapter
102/214
➭ Insert one hexagon socket-head bolt M8x25 (with pan head) each into the now free holes.
Fig. 103: Inserting hexagon socket-head bolts
➭ Clean the silicone adapter and the inside-cone cast-resin socket carefully. Use a cleaning
agent without solvents and a lint-free cloth.
➭ Grease the silicone adapter and the inside-cone cast-resin socket uniformly with mounting
paste for cables sets.
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
Fig. 105: Greasing and cleaning
the inside-cone cast-resin socket