Installation
88/214
➭ Undo 11 bolt-and-washer assemblies M8x40 and 1 hexagonal bolt (with plain washer and
spring washer) at the cover of the panel connection housing ④ .
Fig. 89:
Removing the cover with the plug sockets
➭ Remove the panel connection housing ⑤ .
➭ Take the sealing ring ⑥ out of the groove in the cover of the panel connection housing.
Fig. 90:
Removing the panel
connection housing
➭ Remove 4 pan-head bolts, 4 nuts and 4 strain washers from the cover of the panel
connection housing ⑦ .
NOTE
Do not reuse the removed pan-head bolts, strain washers and nuts.
➭ Dispose of the pan-head bolts, strain washers and nuts in an environmentally
compatible way.
➭ Remove the cover of the panel connection housing ⑦ .
Fig. 91:
Removing the cover of the panel connection housing
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
Cover of panel connection housing
Panel connection housing
Sealing ring
Cover of panel connection housing