Ycas0783 - 0953 (Si) - York Millennium YCAS Series Installation Operation & Maintenance

Air cooled liquid chiller, 3/4 compressor style f 50 hz
Hide thumbs Also See for Millennium YCAS Series:
Table of Contents

Advertisement

Technical Data
All dimensions
are in mm unless
otherwise noted.
CONTROL ENTRY
(12) 22
CONDUIT K.O.'S
229
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres-
sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control
panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be
higher than the unit.
98
DIMENSIONS – YCAS0783 - 0953
711
51
120
51 TYP.
VIEW B-B
B
CONTROL
TRANSFORMER
SERVICE SWITCH
2331
VIEW A-A
178
CONTROL
OPENING
(229 HIGH)
51
305
POWER
OPENING
(533 HIGH)
VIEW C-C
MICRO-COMPUTER
CONTROL CENTER
B
OPTIONS PANEL
C
511
C
112 (EDGE OF
UNIT TO COOLER
CONNECTION)
LD03967
1067
800
191
LD03968