TABLE 4 – CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS
WITH 4 FANS/SYSTEM
Fan
Fans
Stage
1
1
S
2
3
Y
3
5, 7
S
4
1, 5, 7
5
3, 5, 7
1
6
1, 3, 5, 7
1
2
S
2
4
Y
3
6, 8
S
4
2, 6, 8
5
4, 6, 8
2
6
2, 4, 6, 8
Fan
Fans
Stage
1
13
S
2
15
Y
3
17, 19
S
4
13, 17, 19
5
15, 17, 19
3
6
13, 15, 17, 19
* Newer versions of EPROMs will have ON and OFF pressures 15 PSIG below the published values shown above.
TABLE 5 – CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS
WITH 5 FANS/SYSTEM
Fan
Fans
Stage
1
1
S
2
3, 5
Y
3
7, 9
S
4
1, 7, 9
5
3, 5, 7, 9
1
6
1, 3, 5, 7, 9
1
2
S
2
4, 6
Y
3
8, 10
S
4
2, 8, 10
5
4, 6, 8,10
2
6
2, 4, 6, 8, 10
S
Y
S
3
* Newer versions of EPROMs will have ON and OFF pressures (1.0 bar) 15 PSIG below the published values shown above.
174
ON *
OFF *
Conditions
Conditions
DP
DP & OAT
>15.2 BAR
<10.3 BAR & <15.6°C
>16.2 BAR
<11.4 BAR & <18.3°C
>17.2 BAR
<12.4 BAR & <21.1°C
>18.3 BAR
<13.4 BAR & <23.9°C
>19.3 BAR
<14.5 BAR & <26.7°C
>20.0 BAR
<15.2 BAR & <29.4°C
>15.2 BAR
<10.3 BAR & <15.6°C
>16.2 BAR
<11.4 BAR & <18.3°C
>17.2 BAR
<12.4 BAR & <21.1°C
>18.3 BAR
<13.4 BAR & <23.9°C
>19.3 BAR
<14.5 BAR & <26.7°C
>20.0 BAR
<15.2 BAR & <29.4°C
ON *
OFF *
Conditions
Conditions
DP
DP & OAT
>15.2 BAR
<10.3 BAR & <15.6°C
>16.2 BAR
<11.4 BAR & <18.3°C
>17.2 BAR
<12.4 BAR & <21.1°C
>18.3 BAR
<13.4 BAR & <23.9°C
>19.3 BAR
<14.5 BAR & <26.7°C
>20.0 BAR
<15.2 BAR & <29.4°C
ON *
OFF *
Conditions
Conditions
DP
DP & OAT
>15.2 BAR
<10.3 BAR & <15.6°C
>16.2 BAR
<11.4 BAR & <18.3°C
>17.2 BAR
<12.4 BAR & <21.1°C
>18.3 BAR
<13.4 BAR & <23.9°C
>19.3 BAR
<14.5 BAR & <26.7°C
>20.0 BAR
<15.2 BAR & <29.4°C
>15.2 BAR
<10.3 BAR & <15.6°C
>16.2 BAR
<11.4 BAR & <18.3°C
>17.2 BAR
<12.4 BAR & <21.1°C
>18.3 BAR
<13.4 BAR & <23.9°C
>19.3 BAR
<14.5 BAR & <26.7°C
>20.0 BAR
<15.2 BAR & <29.4°C
SYSTEM 3 IS ALWAYS EQUIPPED WITH 4 FANS.
Fan
Contactor
Number
9M
10M
11M, 12M
9M, 11M, 12M
130, 132
10M, 11M, 12M
131, 132
9M, 10M, 11M, 12M
130, 131, 132
15M
16M
17M, 18M
15M, 17M, 18M
230, 232
16M, 17M, 18M
231, 232
15M, 16M, 17M, 18M
230, 231, 232
Fan
Contactor
Number
21M
22M
23M, 24M
21M, 23M, 24M
330, 332
22M, 23M, 24M
331, 332
21M, 22M, 23M, 24M
330, 331, 332
Fan
Contactor
9M
10M, 11M
12M, 13M
9M, 12M, 13M
10M, 11M, 12M, 13M
9M, 10M, 11M, 12M, 13M
130, 131, 132
15M
16M, 17M
18M, 19M
15M, 18M, 19M
16M, 17M, 18M, 19M
15M, 16M, 17M, 18M, 19M
230, 231, 232
Relay
Wire
Board
Output
130
15
131
14
132
10
10,15
10, 14
10, 14, 15
230
15
231
14
232
10
10,15
10, 14
10, 14, 15
I/O Expansion
Wire
Board
Output TB3
330
8
331
9
332
10
8, 10
9, 10
8, 9, 10
Relay
Wire
Board
Number
Output
130
15
131
14
132
10
130, 132
10, 15
131, 132
10, 14
10, 14, 15
230
15
231
14
232
10
230, 232
10, 15
231, 232
10, 14
10, 14, 15